Customization: | Available |
---|---|
Application: | High-voltage |
Material: | Composite Polymer |
Still deciding? Get samples of $ !
Order Sample
|
Shipping Cost: | Contact the supplier about freight and estimated delivery time. |
---|
Payment Methods: |
![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() |
---|---|
Support payments in USD |
Secure payments: | Every payment you make on Made-in-China.com is protected by the platform. |
---|
Refund policy: | Claim a refund if your order doesn't ship, is missing, or arrives with product issues. |
---|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Rated Voltage: | 72.5kV | SCL: | 16kN |
Type: | Station Post | Type Test: | Provide |
Material: | Composite, Polymer | Sample Available: | Yes |
No. | Description | Rated Voltage (kV) |
Specified Mechanical Bending Load (kN) | Section Height H (mm) |
Minimum Arcing Distance H (mm) |
Minimum Creepage DistanceL (mm) | Lightning Impulse Withstand Voltag≥(kV) | Power Frequency Withstand Voltage≥(kV) |
1 | FZSW-66/16 | 66 | 16 | 770±1 | 636 | 1813 | 325 | 130 |
2 | FZSW1-110/10 | 110 | 10 | 1220±2.7 | 1084 | 3150 | 450 | 185 |
3 | FZSW2-138/10 | 138 | 10 | 1200±2 | 1064 | 3150 | 450 | 185 |
4 | FZSW1-110/20 | 110 | 20 | 1220±2.7 | 1044 | 3150 | 450 | 185 |
5 | FZSW2-138/20 | 138 | 20 | 1200±2 | 1024 | 3150 | 450 | 185 |
6 | FZSW - 252/20 (Upper & lower components) |
252 | 20 | 2300±3.8 | 2007 | 6300 | 950 | 395 |
Rated Voltage (kV) |
Height (mm) |
Dry Arcing Distance (mm) |
Creepage Distance (mm) |
Specified Cantilever Load (SCL) |
Max. Design Cantilever Load (MDCL) |
Max. Design Torsion Load (MDTol) |
Dry Power Frequency Withstand Voltage (kV) |
Lightning Impulse Withstand Voltage (kV) |
72.5 | 770±1 | ≥682mm | ≥1813 | ≥16kN | ≥10kN | ≥1.2kN • m | ≥165 | ≥325 |
I. Type Tests
The following type tests as per the relevant standard shall be conducted on the Insulators of identical design to prove that the offered insulator satisfies all the design requirements set out in this specification.
II. Routine Tests
The manufacturer shall carry out, at his own expense, the routine tests; specified in IEC 60383. The routine tensile load shall be 50% of the electromechanical failing load.
MARKING AND LABELLING
Manufacturer's Name or Trademark;
ii) Manufacturer's Type Designation;
iii) Specified Electrical Characteristics;
iv) Specified Mechanical Load.
MARKING
Each insulator unit is marked with the name or trade mark of the manufacturer and the year of manufacture in accordance with IEC 61952 and means to ensure a system of trace-ability for each of the component parts. In addition, each insulator unit is marked with the specified mechanical failing load in conformity with lEC 61952 and client' requirements.
Factory Direct
Countries our insulators reached:United Sates, Canada, Mexico, Honduras, Trinidad and Tobago, Paraguay, Dominican Republic, Brazil, Costa Rica, Argentina, Venezuela, Chile, Peru. Ecuador, Malawi, Ghana.Togo. Egypt, Ethiopia. Mozambique, Samoa. Sweden, Norway. France, Belgium, Czech Republic. Poland. Bulgaria. Romania, Jordan. Oman, Pakistan, Uzbekistan, Afghanistan, Kyrghyzstan, Viet Nam, Cambodia, Philippines, Sri Lanka, Indonesia,Thailand, Papua New Guinea, Australia, Nea Zealand...5 continents 45+ counties.