No. | Description | Rated Voltage (kV) |
Specified Mechanical Bending Load (kN) | Section Height H (mm) |
Minimum Arcing Distance H (mm) |
Minimum Creepage DistanceL (mm) | Lightning Impulse Withstand Voltag≥(kV) | Power Frequency Withstand Voltage≥(kV) |
1 | FZSW-66/16 | 66 | 16 | 770±1 | 636 | 1813 | 325 | 130 |
2 | FZSW1-110/10 | 110 | 10 | 1220±2.7 | 1084 | 3150 | 450 | 185 |
3 | FZSW2-138/10 | 138 | 10 | 1200±2 | 1064 | 3150 | 450 | 185 |
4 | FZSW1-110/20 | 110 | 20 | 1220±2.7 | 1044 | 3150 | 450 | 185 |
5 | FZSW2-138/20 | 138 | 20 | 1200±2 | 1024 | 3150 | 450 | 185 |
6 | FZSW - 252/20 (Upper & lower components) |
252 | 20 | 2300±3.8 | 2007 | 6300 | 950 | 395 |
Rated Voltage | Height | Dry Arcing Distance | Creepage Distance | Specified Cantilever Load (SCL) |
Rod | No. od sheds | Wet Power Frequency Withstand Voltage (kV) |
Lightning Impulse Withstand Voltage (kV) |
35kV | 558±10mm | 375mm | 1200mm | 11.5kN | 50mm | 10 | ≥110 | ≥245 |
Item | Requirement | Measured Valued |
Visual examination | Fuchsine, grey or white, no obvious mechanical admixture. Vulcanized silicon rubber with dense and smooth cutting surface. | Ok |
Hardness (shore A) | ≮50 | 65~70 |
Tensile strength (Map) | ≮4 | 4~6 |
Failure elongation (%) | ≮150 | ≮180 |
Tearing strength (kN/m) | ≮10 (right angle sample) | 12~15 |
Volume resistivity (Ω.m) | 1X1012 | 3~8X1012 |
Puncture strength (kV/mm) | Alternating current ≮22 | ≮30 |
Tracking and erosion | TMA4.5,erosion depth≯2.5mm | TMA4.5, erosion depth <0.8mm |
Flammability (Grade) | FV-0 | FV-0 |